5.b UPDATED Rigwald Solar DrawingsCOVER PAGE CP 0.0 PV SYSTEM AS INDICATED Scale:Project: Connexus Energy EXISTING SUNMODO GROUND MOUNT SITE MAP & PV LAYOUT ELECTRICAL 1-LINE DIAGRAM ATTACHMENT LAYOUT SYSTEM LABELING DETAIL INVERTER DATA SHEET SHEET INDEX PROPERTY PLAN RSD DATA SHEET MODULE DATA SHEET ATTACHMENT DATA SHEET PV 1.0 SYSTEM RATING EQUIPMENT SUMMARY ELECTRICAL INFORMATION MAIN SERVICE PANEL BUS SIZE: MAIN SERVICE BREAKER SIZE: MOUNTING SYSTEM: BUILDING INFORMATION CONSTRUCTION TYPE: V-B OCCUPANCY: R3 VICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS) GENERAL NOTES 1.All electrical materials shall be new and listed by recognized electrical testing laboratory Custom made equipment shall have complete test data submitted by the manufacturer attesting to its safety 2.Outdoor equipment shall be NEMA 3R rated or equivalent 3.All metallic equipment shall be grounded 4.Contractor shall obtain electrical permits prior to installation and shall coordinate all inspections, testing commissioning and acceptance with the client, utility co. and city inspectors as needed. 5.The electrical contractor shall verify the exact locations of service points and service sizes with the serving utility company and comply with all utility companies requirements. 6.Drawings are diagrammatic only, routing of raceways shall be option of the contractor unless otherwise noted and shall be coordinated with other trades. 7.If the roof material or the roof structure not adequate for PV installation, call the engineer of record prior to installation. The contractor is responsible to verify that the roof is capable of withstanding the extra weight. 8.If the distances for cable runs are different than shown, the contractor shall notify the electrical engineer to validate the wire size. Final drawings will be red-lined and updated as appropriate. 9.Whenever a discrepancy in quality of equipment arises on the drawing or specifications, the contractor shall be responsible for providing and installing all materials and services required by the strictest conditions noted on the drawings or in the specifications to ensure complete compliance and longevity of the operable system required by the engineer of record. PHOTOVOLTAIC NOTES: 1.Ground mounted photovoltaic panels and modules shall be tested, listed and identified by recognized testing laboratory 2.Solar system shall not cover any plumbing or mechanical vents 3.Modules and support structures shall be grounded unless racking has integrated ground. 4.Removal of an interactive inverter or other equipment shall not disconnect the bonding connection between the grounding electrode conductor and the photovoltaic source and/or output circuit grounded conductors. 5.All PV modules and associated equipment and wiring shall be protected from physical damage. 6.Live parts of PV source circuits and PV output circuits over 150v to ground shall not be accessible to other than qualified persons while energized. 7.Inverter is equipped with integrated DC disconnect, thus providing ground fault protection 8.All conductors shall be copper and 75 deg rated 9.A single conductor shall be permitted to be used to perform the multiple functions of dc grounding, AC grounding and bonding between AC and DC systems. 10.Non-current carrying metal parts of equipment shall be effectively bonded together. Bond both ends of raceways. 200A 200A WAAREE 400 WATT MODULES INTEGRATED IQ7HS MICROINVERTERS THE INSTALLATION OF SOLAR ARRAYS AND PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH THE FOLLOWING CODES: ·2023 National Electrical Code ·2018 International Building Code ·2018 International Residential Code ·2020 Minnesota Residential Code ·2020 Minnesota Building Code ·2020 Minnesota Energy Code ·2020 Minnesota Accessibility Code ·2020 Minnesota State Fire Code ·2018 International Fire Code ·2018 International Energy Conservation Code ·2018 Mechanical Code AS ADOPTED BY THE STATE OF MINNESOTA ALL OTHER ORDINANCE ADOPTED BY THE LOCAL GOVERNING AGENCIES GOVERNING CODES SURGE PROTECTION PLACARD DC 28.00 KW STC AC 26.88 KW STC 70 PV 2.0 PV 3.1 PV 3.2 PV 4.0 PV 5.1 D 6.0 D 7.0 D 8.0 D 9.0 D 10.0 D 11.0 D 12.0 D 13.0 COVER PAGE CP 0.0 70 INVERTER CERTIFICATION UTILITY Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE: REVISION DATE: Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE: 09/15/2023 MONITORING DATA SHEET RACKING DATA SHEET These drawings are protected by copyright under US law. Any form of reproduction is strictly prohibited without prior written approval from Engineerinc. PV INSPECTION CHECKLIST D 14.0 CONNECTOR DATA SHEET D 15.0 INDEX NOTE: Conduit in attic shall be minimum 18 inches from roof sheating Note: 24/ 7 Unescorted keyless access is to be provided for ALL UTILITY EQUIPMENT NOTE: No clearance issue Distance between all equipments is maximum 10" SECONDARY INTERCONNECTION SOLAR MODULES ___ WAAREE 400 Watt Model #SUNPOWER U-SERIES INVERTER INVERTER TYPE: Micro: ___ Enphase IQ7HS Microinverters Model # IQ7HS-66M-US(240V) Connexus Energy SITE MAP & PV LAYOUT PV 1.0 PV SYSTEM AS INDICATED Scale:Project: 70 70 Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 ....................... ........................ ................ ............. MSP (E) Main Service Panel UAC.................(N) 200A Utility AC (N) Microinverter PVS (N) PV Sub Panel................... (E) Main MeterMM........................ ............. JB (N) Junction Box (N) Solar Module EMT Type Conduit PVC type Conduit PVS6....(N) PV Monitoring System 200A BD ............(N) Breaker Disconnect EQUIPMENT ELEVATION NOTE: Keep 3ft clearance from gas meter and AC unit From Ground Mount Solar PV Array Main Service Panel PV Sub Panel Utility AC Disconnect Main Meter Breaker Disconnect 4-4-4-4 AL Underground Feeder In s i d e Ou t s i d e From Ground Mount Solar PV Array PV Sub Panel Breaker Disconnect PVS6 PVC BOX PB.............................(N) PVC Box 4/0-4/0-4/0-2/0 URD Underground Feeder MM JB PVS BD JB PVS BD aaaaaaaaaa b c b c b c b c b c b c b c b c b c b c d e f g d e f g d e f g d e f g d e f g d e f g d e f g d e f g d e f g d e f g Ground Mount Solar PV Array 1 30 - Waaree 400W Modules 30 - Integrated IQ7HS Microinverters Pitch: 35 Deg Orientation: 180 Deg Ground Mount Solar PV Array 2 40 - Waaree 400W Modules 40 - Integrated IQ7HS Microinverters Pitch: 35 Deg Orientation: 180 Deg 4-4-4-4 AL Underground Feeder UAC MSP 185th St N PB PVS6 4/0-4/0-4/0-2/0 URD Underground Feeder SCALE:1/32" = 1'-0" 180° 90° 270° 0° S W N E ELECTRICAL 1-LINE DIAGRAM PV 2.0 PV SYSTEM AS INDICATED Scale:Project: Note: 24/ 7 Unescorted keyless access is to be provided for ALL UTILITY EQUIPMENT Design meet National Electric Code(NEC codes) SUNPOWER U-SERIES 400 WATT MODULES70 INTEGRATED ENPHASE IQ7HS MICROINVERTERS SYSTEM RATING AND DER POWER OUTPUT INVERTER:ENPHASE IQ7HS INVERTER MAXIMUM CONTINUOUS OUTPUT:384VA SYSTEM POWER OUTPUT: ENPHASE MICROINVERTERS 1 PHASE 384VA MAXIMUM OUTPUT CURRENT 1.6A AC PORT BACKFEED CURRENT 0A DC SHORT CIRCUIT CURRENT 15A DC 28.00 KW STC AC 26.88 KW STC DC 28.00 KW STC AC 26.88 KW STC Connexus Energy x 384 =11.52 SECONDARY INTERCONNECTION REFERENCE POINT OF APPLICABILITY 200A PV SUB PANEL 120/240V, NEMA 3R INSTALL (4)20A PV 2-POLE C/B 112A NOTE: Keep 3ft clearance from gas meter and AC unit 70 70 Wire Size 90C wire rating 12 AWGTHWN-2, THHN XHHW-2, USE-2 10 AWGTHWN-2, THHN XHHW-2, USE-3 8 AWGTHWN-2, THHN XHHW-2, USE-4 30 40 55 Temperature rating of Conductors-Ambient Temp. (114-122F) NEC 310.15(B)(2)(a) Number of Current carrying Conductors NEC 310.15(B)(16) 4-6 7-9 10-20 20A Branch Circuit Rating 30A Branch Circuit Rating 30 x 0.82=24.6 40 x 0.82=32.8 55 x 0.82=45.1 24.6x0.80= 19.68 32.8x0.80= 26.24 45.1x0.80= 36.08 24.6x0.70= 17.22 32.8x0.70= 22.96 45.1x0.70= 31.57 24.6x0.50= 12.3 32.8x0.50= 16.4 45.1x0.50= 22.55 YES- 6 or less current carrying conductors in the same conduit YES- 9 or less current carrying conductors in the same conduit YES- 20 or less current carrying conductors in the same conduit YES- 9 or less current carrying conductors in the same conduit YES- 3 or less current carrying conductors in the same conduit NO Surge Protection MNSPD-300-AC Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 (8) #10 AWG THWN/THWN-2 (1)#10 AWG GND 3/4" EMT, 2 FEET (3) #4/0 AWG THWN/THWN-2 (1) #6 AWG GND 1" SCH 80 PVC, 2 FEET ENPHASE Q CABLE (2) #12 AWG PV WIRE (1) #6 AWG EGC FREE IN THE AIR 1 BR A N C H CI R C U I T - G (1) J BOX NEMA3R 16A 1-PHASE MICRO-INVERTER UL1741 2 10 1 16A 2 10 BR A N C H CI R C U I T - F EXISTING ______ MAIN SERVICE PANEL 120/240V, 1P, 3W 200A 200A BREAKER DISCONNECT (NEW)GEC Add 2nd Ground rod and tie it to the existing ground rod. EXISTING NON CENTER _____ MAIN C/B 112A 200A200A FUSED UTILITY AC DISCONNECT, WITH 150A FUSES, VISIBLE-OPEN LOCKABLE, READILY ACCESSIBLE, NEMA3R, 120 / 240V (3) #4/0 AL AWG THWN/THWN-2 (1) #4/0AL AWG GND 2" SCH 80 PVC, 2 FEET 4/0-4/0-4/0-2/0 URD Underground Feeder (3) #4/0 AL AWG THWN/THWN-2 (1) #4 AWG GND 2" SCH 80 PVC, 2 FEET (3) #4/0 AWG THWN/THWN-2 2" SCH 80 PVC, 2 FEET (1) #6 AWG GND UTILITY METER 120/240V, 1P, 3W GEC (E) GROUNDING ELECTRODE SYSTEM 15A PVS6 MONITORING SYSTEM Production CTs 1 16A 2 10 BR A N C H CI R C U I T - E 112A 1 16A 2 10 BR A N C H CI R C U I T - D 1 BR A N C H CI R C U I T - C (1) J BOX NEMA3R 16A 1-PHASE MICRO-INVERTER UL1741 2 10 1 16A 2 10 BR A N C H CI R C U I T - B 1 16A 2 10 BR A N C H CI R C U I T - A 125A PV SUB PANEL 120/240V, NEMA 3R INSTALL (3)20A PV 2-POLE C/B 60A BREAKER DISCONNECT 60A INSTALL (1)60A PV 2-POLE C/B (3) #4 AL AWG THWN/THWN-2 (1) #4 AWG GND 3/4" SCH 80 PVC, 2 FEET 4-4-4-4 AL Underground Feeder (3) #4 AL AWG THWN/THWN-2 (1) #4 AWG GND 3/4" SCH 80 PVC, 2 FEET (3) #6 AWG THWN/THWN-2 (1) #6 AWG GND 3/4" SCH 80 PVC, 2 FEET (6) #10 AWG THWN/THWN-2 (1)#10 AWG GND 3/4" EMT, 2 FEET ENPHASE Q CABLE (2) #12 AWG PV WIRE (1) #6 AWG EGC FREE IN THE AIR 48A 48A 150A NSI TS250-2 Lugs 6X6 PVC BOX SYSTEM LABELING DETAIL PV 3.1 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 PV ARRAY J BOX PV SUB-PANEL AC DISCONNECT MAIN SERVICE PANEL METER 2 3 3 3 2 17 16 21 8 13 5 Note: LABELS SHALL COMPLY WITH NEC 690 “Labels shall be weatherproof, durable and permanently mounted” Photovoltaic Power Source LABEL 2 CAUTION: SOLAR CIRCUIT LABEL 3 WARNING ELECTRIC SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNDERGROUND AND MAY BE ENERGIZED LABEL 4 WARNING ELECTRIC SHOCK HAZARD IF GROUND FAULT IS INDICATED NORMALLY GROUNDED CONDUCTORS MAY BE UNDERGROUND AND ENERGIZED LABEL 5 WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION LABEL 6 WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT LABEL 7 WARNING LABEL 8 TURN OF PHOTOVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL DO NOT DISCONNECT UNDER LOAD LABEL 9 MAIN PV SYSTEM DISCONNECT LABEL 10 MAIN PV SYSTEM AC DISCONNECT LABEL 11 LABEL 12 CAUTION LABEL 13 SOLAR ELECTRIC SYSTEM CONNECTED WARNING- LABEL 14 DUAL POWER SOURCE SECOND SOURCE IS PV SYSTEM CAUTION LABEL 15 PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED LABEL 16 PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT MAXIMUM AC OPERATING CURRENT PHOTOVOLTAIC LABEL 17 UTILITY AC DISCONNECT PHOTOVOLTAIC LABEL 18 DC DISCONNECT NOMINAL OPERATING AC VOLTAGE NOMINAL OPERATING AC FREQUANCY MAXIMUM AC POWER MAXIMUM AC CURRENT MAX OCERCURRENT DEVICE RATING FOR AC MODULE PROTECTION LABEL 19 LABEL 20 PV SYSTEM DC DISCONNECT OPERATING CURRENT OPERATING VOLTAGE MAXIMUM SYSTEM VOLTAGE SHORT CIRCUIT CURRENT RATED MAX POWER-FONT CURRENT RATED MAX POWER-FONT VOLTAGE MAXIMUM SYSTEM VOLTAGE SHORT CIRCUIT CURRENT MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER IF INSTALLED LABEL 21 ***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted 240V SOLAR DISCONNECT 21 SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY SOLAR ELECTRIC PV PANELS 112A Production Meter LABEL 1 Performance Meter 3 1 PLACARD PV 3.2 PV SYSTEM AS INDICATED Scale:Project: CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: SERVICE 1 OF 2 CAUTION POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN: SERVICE 2 OF 2 N W E S N W E S14025 185th St N, Marine on St Croix, MN 55047 14025 185th St N, Marine on St Croix, MN 55047 Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 PV SYSTEM DISCONNECT FOR UTILITY OPERATION UTILITY METER MAIN SERVICE PANEL BREAKER DISCONNECT PV SUB PANEL BREAKER DISCONNECT PV SUB PANEL SOLAR PV ARRAY SOLAR PV ARRAY 6X6 PVC BOX PV MONITORING DEVICE PV SYSTEM DISCONNECT FOR UTILITY OPERATION UTILITY METER MAIN SERVICE PANEL BREAKER DISCONNECT PV SUB PANEL BREAKER DISCONNECT PV SUB PANEL SOLAR PV ARRAY SOLAR PV ARRAY 6X6 PVC BOX PV MONITORING DEVICE PROPERTY PLAN PV 4.0 PV SYSTEM AS INDICATED Scale:Project: ..................... MSP Main Service Panel INDEX AC ..................................Utility AC PVS PV Sub Panel ...................... Main MeterMM.............................. Solar Module ................. Note: 24/ 7 Unescorted keyless access is to be provided for ALL UTILITY EQUIPMENT Connexus Energy Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 PVS6 PV Monitoring System............ PD Pullout Disconnect ................. PB...................................PVC Box PROPERTY LINE POND POND POND POND POND POOL DRIVEWAY 603'-8" 547'-8" 1084'-11" 1302'-2" 479'-7" 751'-9" 250' 977'-7" 268'-9" 89'-3" MM PVS BD PVS BD UAC MSP 395'-1" 185th St N PB PVS6 20' SCALE:1/64" = 1'-0" 180° 90° 270° 0° S W N E ATTACHMENT LAYOUT PV 5.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 Note: 24/ 7 Unescorted keyless access is to be provided for ALL UTILITY EQUIPMENT RAIL ATTACHMENT 2" HORIZONTAL PIPE POINT LOAD CALCULATION PER ARRAY 1 Module Weight (lbs) # Of Modules 48.5 Total Module Weight (lbs) Rack Weight (lbs) Total System Weight (lbs) # Of Standoffs Max Span Between Standoffs (in) Loading Per Standoff (lbs) Loading (PSF) 1940 388 2328 18 96 129.33 2.64 40 160" 26 in 78" 35° 18" Auger depth and spacing calculated by engineer Au g e r 8 t o 9 f t Formed steel "T" rail (see detail) Items are listed in the fault current path in order from the PV Panel to the Post Base 1. PV Panel 2. Grounding Mid Clamp Kit 3. Helio Rail 4. 2" Aluminium Pipe Clamp Kit with PVC insulator 5. Horizontal Steel Post 6. 2" Pipr Splice Kit (configuration dependent) 7. 2" T Pipe Cap Kit 8. Vertical Post 9. 2" Post Base Kit 10. Grounding Lug Module Area (sq.ft.)880 Crow Wing Power POINT LOAD CALCULATION PER ARRAY 2 Module Weight (lbs) # Of Modules 48.5 Total Module Weight (lbs) Rack Weight (lbs) Total System Weight (lbs) # Of Standoffs Max Span Between Standoffs (in) Loading Per Standoff (lbs) Loading (PSF) 1455 291 1746 18 96 97 2.64 30 Module Area (sq.ft.)660 8'8'8'8'8'8'8'8' 8'8'8'8'8'8'8'8' 6'-6" 3'-5" 3'-5" 6'-6" 1'-9" 1'-9" 65' 65' ARRAY 1 ARRAY 2 PV 6.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 MONITORING DATA SHEET INVERTER DATA SHEET D 7.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 RSD DATA SHEET D 8.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 MODULE DATA SHEET D 9.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE: REVISION DATE: Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE: 09/15/2023 RACKING DATA SHEET D 10.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 ATTACHMENT DATA SHEET D 11.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 D 12.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 SURGE PROTECTION D 13.0 PV SYSTEM AS INDICATED Scale:Project: INVERTER CERTIFICATION Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 D 14.0 PV SYSTEM AS INDICATED Scale:Project: PV INSPECTION CHECKLIST Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 Wolf RIver Electric Marine on St Croix, MN 5504714025 185th St N D 15.0 PV SYSTEM AS INDICATED Scale:Project: Drawn by: New@engineerinc.io Project Name: Property Address: DATE CREATED: CONTRACTOR Wolf RIver Electric Address:101 Isanti Parkway NE, Isanti, MN 55040 Phone number: (763) 229-6662 E-mail: contact@wolfriverelectric.com REVISION DATE: 08/14/2023 14025 185th St N, Marine on St Croix, MN 55047 REVISION DATE: REVISION DATE : REVISION DATE : Brian Rigwald 08/11/2023 REVISION DATE: REVISION DATE : 09/15/2023 CONNECTOR DATA SHEET