5.b UPDATED Rigwald Solar DrawingsCOVER PAGE
CP 0.0
PV SYSTEM AS INDICATED
Scale:Project:
Connexus Energy
EXISTING
SUNMODO GROUND MOUNT
SITE MAP & PV LAYOUT
ELECTRICAL 1-LINE DIAGRAM
ATTACHMENT LAYOUT
SYSTEM LABELING DETAIL
INVERTER DATA SHEET
SHEET INDEX
PROPERTY PLAN
RSD DATA SHEET
MODULE DATA SHEET
ATTACHMENT DATA SHEET
PV 1.0
SYSTEM RATING
EQUIPMENT SUMMARY
ELECTRICAL INFORMATION
MAIN SERVICE PANEL BUS SIZE:
MAIN SERVICE BREAKER SIZE:
MOUNTING SYSTEM:
BUILDING INFORMATION
CONSTRUCTION TYPE: V-B
OCCUPANCY: R3
VICINITY MAP (SCALE: NTS)SATELLITE VIEW (SCALE: NTS)
GENERAL NOTES
1.All electrical materials shall be new and listed by recognized
electrical testing laboratory
Custom made equipment shall have complete test data submitted
by the manufacturer attesting to its safety
2.Outdoor equipment shall be NEMA 3R rated or equivalent
3.All metallic equipment shall be grounded
4.Contractor shall obtain electrical permits prior to installation and
shall coordinate all inspections, testing commissioning and
acceptance with the client,
utility co. and city inspectors as needed.
5.The electrical contractor shall verify the exact locations of service
points and service sizes with the serving utility company and
comply with all utility companies requirements.
6.Drawings are diagrammatic only, routing of raceways shall be
option of the contractor unless otherwise noted and shall be
coordinated with other trades.
7.If the roof material or the roof structure not adequate for PV
installation, call the engineer of record prior to installation. The
contractor is responsible to verify that the roof is capable of
withstanding the extra weight.
8.If the distances for cable runs are different than shown, the
contractor shall notify the electrical engineer to validate the wire
size. Final drawings will be red-lined and updated as appropriate.
9.Whenever a discrepancy in quality of equipment arises on the
drawing or specifications, the contractor shall be responsible for
providing and installing all materials and services required by the
strictest conditions noted on the drawings or in the specifications
to ensure complete compliance and longevity of the operable
system required by the engineer of record.
PHOTOVOLTAIC NOTES:
1.Ground mounted photovoltaic panels and modules shall be tested,
listed and identified by recognized testing laboratory
2.Solar system shall not cover any plumbing or mechanical vents
3.Modules and support structures shall be grounded
unless racking has integrated ground.
4.Removal of an interactive inverter or other equipment shall not
disconnect the bonding connection between the grounding
electrode conductor and the photovoltaic source and/or output
circuit grounded conductors.
5.All PV modules and associated equipment and wiring shall be
protected from physical damage.
6.Live parts of PV source circuits and PV output circuits over 150v to
ground shall not be accessible to other than qualified persons
while energized.
7.Inverter is equipped with integrated DC disconnect, thus providing
ground fault protection
8.All conductors shall be copper and 75 deg rated
9.A single conductor shall be permitted to be used to perform the
multiple functions of dc grounding, AC grounding and bonding
between AC and DC systems.
10.Non-current carrying metal parts of equipment shall be effectively
bonded together. Bond both ends of raceways.
200A
200A
WAAREE 400 WATT MODULES
INTEGRATED IQ7HS MICROINVERTERS
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY WITH
THE FOLLOWING CODES:
·2023 National Electrical Code
·2018 International Building Code
·2018 International Residential Code
·2020 Minnesota Residential Code
·2020 Minnesota Building Code
·2020 Minnesota Energy Code
·2020 Minnesota Accessibility Code
·2020 Minnesota State Fire Code
·2018 International Fire Code
·2018 International Energy Conservation Code
·2018 Mechanical Code
AS ADOPTED BY THE STATE OF MINNESOTA
ALL OTHER ORDINANCE ADOPTED BY THE
LOCAL GOVERNING AGENCIES
GOVERNING CODES
SURGE PROTECTION
PLACARD
DC 28.00 KW STC
AC 26.88 KW STC
70
PV 2.0
PV 3.1
PV 3.2
PV 4.0
PV 5.1
D 6.0
D 7.0
D 8.0
D 9.0
D 10.0
D 11.0
D 12.0
D 13.0
COVER PAGE CP 0.0
70
INVERTER CERTIFICATION
UTILITY
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE:
REVISION DATE:
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE: 09/15/2023
MONITORING DATA SHEET
RACKING DATA SHEET
These drawings are protected by copyright under US law. Any form of
reproduction is strictly prohibited without prior written approval from Engineerinc.
PV INSPECTION CHECKLIST D 14.0
CONNECTOR DATA SHEET D 15.0
INDEX
NOTE: Conduit in attic shall
be minimum 18 inches from roof sheating
Note: 24/ 7 Unescorted keyless access is to be
provided for ALL UTILITY EQUIPMENT
NOTE: No clearance issue
Distance between all equipments is maximum 10"
SECONDARY INTERCONNECTION
SOLAR MODULES
___ WAAREE 400 Watt
Model #SUNPOWER U-SERIES
INVERTER
INVERTER TYPE: Micro:
___ Enphase IQ7HS Microinverters
Model # IQ7HS-66M-US(240V)
Connexus Energy
SITE MAP & PV
LAYOUT
PV 1.0
PV SYSTEM AS INDICATED
Scale:Project:
70
70
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
.......................
........................
................
.............
MSP (E) Main Service Panel
UAC.................(N) 200A Utility AC
(N) Microinverter
PVS (N) PV Sub Panel...................
(E) Main MeterMM........................
.............
JB (N) Junction Box
(N) Solar Module
EMT Type Conduit
PVC type Conduit
PVS6....(N) PV Monitoring System
200A
BD ............(N) Breaker Disconnect
EQUIPMENT ELEVATION
NOTE: Keep 3ft clearance from gas meter and AC unit
From Ground
Mount Solar PV Array
Main
Service
Panel
PV
Sub
Panel
Utility AC
Disconnect
Main
Meter
Breaker
Disconnect
4-4-4-4 AL
Underground Feeder
In
s
i
d
e
Ou
t
s
i
d
e
From Ground
Mount Solar PV Array
PV
Sub
Panel
Breaker
Disconnect
PVS6
PVC
BOX
PB.............................(N) PVC Box
4/0-4/0-4/0-2/0 URD
Underground Feeder
MM
JB
PVS
BD
JB
PVS
BD
aaaaaaaaaa
b
c
b
c
b
c
b
c
b
c
b
c
b
c
b
c
b
c
b
c
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
d
e
f
g
Ground Mount Solar PV Array 1
30 - Waaree 400W Modules
30 - Integrated IQ7HS Microinverters
Pitch: 35 Deg
Orientation: 180 Deg
Ground Mount Solar PV Array 2
40 - Waaree 400W Modules
40 - Integrated IQ7HS Microinverters
Pitch: 35 Deg
Orientation: 180 Deg
4-4-4-4 AL Underground Feeder
UAC
MSP
185th St N
PB
PVS6
4/0-4/0-4/0-2/0 URD
Underground Feeder
SCALE:1/32" = 1'-0"
180°
90° 270°
0°
S
W
N
E
ELECTRICAL 1-LINE
DIAGRAM
PV 2.0
PV SYSTEM AS INDICATED
Scale:Project:
Note: 24/ 7 Unescorted keyless access is to be
provided for ALL UTILITY EQUIPMENT
Design meet National Electric Code(NEC codes)
SUNPOWER U-SERIES 400 WATT MODULES70
INTEGRATED ENPHASE IQ7HS MICROINVERTERS
SYSTEM RATING AND DER POWER OUTPUT
INVERTER:ENPHASE IQ7HS
INVERTER MAXIMUM CONTINUOUS OUTPUT:384VA
SYSTEM POWER OUTPUT:
ENPHASE MICROINVERTERS
1 PHASE 384VA
MAXIMUM OUTPUT CURRENT 1.6A
AC PORT BACKFEED CURRENT 0A
DC SHORT CIRCUIT CURRENT 15A
DC 28.00 KW STC
AC 26.88 KW STC
DC 28.00 KW STC
AC 26.88 KW STC
Connexus Energy
x 384 =11.52
SECONDARY INTERCONNECTION REFERENCE POINT OF APPLICABILITY
200A PV SUB PANEL
120/240V, NEMA 3R
INSTALL (4)20A
PV 2-POLE C/B
112A
NOTE: Keep 3ft clearance from gas meter and AC unit
70
70
Wire Size
90C wire
rating
12 AWGTHWN-2, THHN
XHHW-2, USE-2
10 AWGTHWN-2, THHN
XHHW-2, USE-3
8 AWGTHWN-2, THHN
XHHW-2, USE-4
30
40
55
Temperature rating of
Conductors-Ambient Temp.
(114-122F) NEC 310.15(B)(2)(a)
Number of Current carrying Conductors NEC 310.15(B)(16)
4-6 7-9 10-20 20A Branch Circuit Rating 30A Branch Circuit Rating
30 x 0.82=24.6
40 x 0.82=32.8
55 x 0.82=45.1
24.6x0.80= 19.68
32.8x0.80= 26.24
45.1x0.80= 36.08
24.6x0.70= 17.22
32.8x0.70= 22.96
45.1x0.70= 31.57
24.6x0.50= 12.3
32.8x0.50= 16.4
45.1x0.50= 22.55
YES- 6 or less current carrying
conductors in the same conduit
YES- 9 or less current carrying
conductors in the same conduit
YES- 20 or less current carrying
conductors in the same conduit
YES- 9 or less current carrying
conductors in the same conduit
YES- 3 or less current carrying
conductors in the same conduit
NO
Surge Protection
MNSPD-300-AC
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
(8) #10 AWG THWN/THWN-2
(1)#10 AWG GND
3/4" EMT, 2 FEET
(3) #4/0 AWG THWN/THWN-2
(1) #6 AWG GND
1" SCH 80 PVC, 2 FEET
ENPHASE Q CABLE
(2) #12 AWG PV WIRE
(1) #6 AWG EGC
FREE IN THE AIR
1
BR
A
N
C
H
CI
R
C
U
I
T
-
G
(1) J BOX
NEMA3R
16A
1-PHASE MICRO-INVERTER UL1741
2 10
1
16A
2 10
BR
A
N
C
H
CI
R
C
U
I
T
-
F
EXISTING
______ MAIN
SERVICE
PANEL
120/240V,
1P, 3W
200A
200A BREAKER
DISCONNECT
(NEW)GEC
Add 2nd Ground rod and
tie it to the existing ground rod.
EXISTING
NON CENTER _____
MAIN C/B
112A
200A200A FUSED UTILITY AC
DISCONNECT,
WITH 150A FUSES,
VISIBLE-OPEN LOCKABLE,
READILY ACCESSIBLE,
NEMA3R, 120 / 240V
(3) #4/0 AL AWG THWN/THWN-2
(1) #4/0AL AWG GND
2" SCH 80 PVC, 2 FEET
4/0-4/0-4/0-2/0 URD Underground Feeder
(3) #4/0 AL AWG THWN/THWN-2
(1) #4 AWG GND
2" SCH 80 PVC, 2 FEET
(3) #4/0 AWG THWN/THWN-2
2" SCH 80 PVC, 2 FEET
(1) #6 AWG GND
UTILITY METER
120/240V,
1P, 3W
GEC
(E) GROUNDING
ELECTRODE SYSTEM
15A
PVS6
MONITORING
SYSTEM
Production CTs
1
16A
2 10
BR
A
N
C
H
CI
R
C
U
I
T
-
E
112A
1
16A
2 10
BR
A
N
C
H
CI
R
C
U
I
T
-
D
1
BR
A
N
C
H
CI
R
C
U
I
T
-
C
(1) J BOX
NEMA3R
16A
1-PHASE MICRO-INVERTER UL1741
2 10
1
16A
2 10
BR
A
N
C
H
CI
R
C
U
I
T
-
B
1
16A
2 10
BR
A
N
C
H
CI
R
C
U
I
T
-
A
125A PV SUB PANEL
120/240V, NEMA 3R
INSTALL (3)20A
PV 2-POLE C/B
60A BREAKER
DISCONNECT
60A
INSTALL (1)60A
PV 2-POLE C/B
(3) #4 AL AWG THWN/THWN-2
(1) #4 AWG GND
3/4" SCH 80 PVC, 2 FEET
4-4-4-4 AL Underground Feeder
(3) #4 AL AWG THWN/THWN-2
(1) #4 AWG GND
3/4" SCH 80 PVC, 2 FEET
(3) #6 AWG THWN/THWN-2
(1) #6 AWG GND
3/4" SCH 80 PVC, 2 FEET
(6) #10 AWG THWN/THWN-2
(1)#10 AWG GND
3/4" EMT, 2 FEET
ENPHASE Q CABLE
(2) #12 AWG PV WIRE
(1) #6 AWG EGC
FREE IN THE AIR
48A 48A
150A
NSI TS250-2 Lugs
6X6 PVC BOX
SYSTEM
LABELING DETAIL
PV 3.1
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
PV ARRAY
J BOX
PV SUB-PANEL
AC
DISCONNECT
MAIN SERVICE
PANEL
METER
2
3
3
3
2
17 16
21 8
13
5
Note: LABELS SHALL COMPLY WITH NEC 690
“Labels shall be weatherproof, durable and permanently mounted”
Photovoltaic Power Source
LABEL 2
CAUTION: SOLAR CIRCUIT
LABEL 3
WARNING
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE
UNDERGROUND AND MAY BE ENERGIZED
LABEL 4
WARNING
ELECTRIC SHOCK HAZARD
IF GROUND FAULT IS INDICATED
NORMALLY GROUNDED CONDUCTORS
MAY BE UNDERGROUND AND ENERGIZED
LABEL 5
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD
SIDES MAY BE ENERGIZED IN THE OPEN
POSITION
LABEL 6
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD
SIDES MAY BE ENERGIZED IN THE OPEN
POSITION
DC VOLTAGE IS ALWAYS PRESENT
WHEN SOLAR MODULES
ARE EXPOSED TO SUNLIGHT
LABEL 7
WARNING
LABEL 8
TURN OF PHOTOVOLTAIC
AC DISCONNECT PRIOR TO
WORKING INSIDE PANEL
DO NOT DISCONNECT
UNDER LOAD
LABEL 9
MAIN PV SYSTEM
DISCONNECT
LABEL 10
MAIN PV SYSTEM
AC DISCONNECT
LABEL 11
LABEL 12
CAUTION
LABEL 13
SOLAR ELECTRIC SYSTEM
CONNECTED
WARNING-
LABEL 14
DUAL POWER SOURCE
SECOND SOURCE IS PV SYSTEM
CAUTION
LABEL 15
PHOTOVOLTAIC SYSTEM CIRCUIT
IS BACKFED
LABEL 16
PHOTOVOLTAIC AC DISCONNECT
MAXIMUM AC OPERATING CURRENT
MAXIMUM AC OPERATING CURRENT
PHOTOVOLTAIC
LABEL 17
UTILITY AC DISCONNECT
PHOTOVOLTAIC
LABEL 18
DC DISCONNECT
NOMINAL OPERATING AC VOLTAGE
NOMINAL OPERATING AC FREQUANCY
MAXIMUM AC POWER
MAXIMUM AC CURRENT
MAX OCERCURRENT DEVICE RATING
FOR AC MODULE PROTECTION
LABEL 19
LABEL 20
PV SYSTEM DC DISCONNECT
OPERATING CURRENT
OPERATING VOLTAGE
MAXIMUM SYSTEM VOLTAGE
SHORT CIRCUIT CURRENT
RATED MAX POWER-FONT CURRENT
RATED MAX POWER-FONT VOLTAGE
MAXIMUM SYSTEM VOLTAGE
SHORT CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER IF INSTALLED
LABEL 21
***ALL LABELS = RED THERMOPLASTIC/REFLECTIVE , Permanently mounted
240V
SOLAR DISCONNECT
21
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
112A
Production Meter
LABEL 1
Performance
Meter
3
1
PLACARD
PV 3.2
PV SYSTEM AS INDICATED
Scale:Project:
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
SERVICE 1 OF 2
CAUTION
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS LOCATED AS SHOWN:
SERVICE 2 OF 2
N
W E
S
N
W E
S14025 185th St N,
Marine on St Croix, MN 55047
14025 185th St N,
Marine on St Croix, MN 55047
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
UTILITY METER
MAIN SERVICE PANEL
BREAKER DISCONNECT
PV SUB PANEL
BREAKER DISCONNECT
PV SUB PANEL
SOLAR PV ARRAY
SOLAR PV ARRAY
6X6 PVC BOX
PV MONITORING DEVICE
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
UTILITY METER
MAIN SERVICE PANEL
BREAKER DISCONNECT
PV SUB PANEL
BREAKER DISCONNECT
PV SUB PANEL
SOLAR PV ARRAY
SOLAR PV ARRAY
6X6 PVC BOX
PV MONITORING DEVICE
PROPERTY PLAN
PV 4.0
PV SYSTEM AS INDICATED
Scale:Project:
.....................
MSP Main Service Panel
INDEX
AC ..................................Utility AC
PVS PV Sub Panel ......................
Main MeterMM..............................
Solar Module
.................
Note: 24/ 7 Unescorted keyless access is to be
provided for ALL UTILITY EQUIPMENT
Connexus Energy
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
PVS6 PV Monitoring System............
PD Pullout Disconnect .................
PB...................................PVC Box
PROPERTY LINE
POND
POND
POND
POND
POND
POOL
DRIVEWAY
603'-8"
547'-8"
1084'-11"
1302'-2"
479'-7"
751'-9"
250'
977'-7"
268'-9"
89'-3"
MM
PVS
BD
PVS
BD
UAC
MSP
395'-1"
185th St N
PB
PVS6
20'
SCALE:1/64" = 1'-0"
180°
90° 270°
0°
S
W
N
E
ATTACHMENT
LAYOUT
PV 5.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
Note: 24/ 7 Unescorted keyless access is to be
provided for ALL UTILITY EQUIPMENT
RAIL
ATTACHMENT
2" HORIZONTAL PIPE
POINT LOAD CALCULATION PER ARRAY 1
Module Weight (lbs)
# Of Modules
48.5
Total Module Weight (lbs)
Rack Weight (lbs)
Total System Weight (lbs)
# Of Standoffs
Max Span Between Standoffs (in)
Loading Per Standoff (lbs)
Loading (PSF)
1940
388
2328
18
96
129.33
2.64
40
160"
26 in
78"
35°
18"
Auger depth and spacing
calculated by engineer
Au
g
e
r
8
t
o
9
f
t
Formed steel "T" rail
(see detail)
Items are listed in the fault current path in order from the PV Panel to the Post Base
1. PV Panel
2. Grounding Mid Clamp Kit
3. Helio Rail
4. 2" Aluminium Pipe Clamp Kit with PVC insulator
5. Horizontal Steel Post
6. 2" Pipr Splice Kit (configuration dependent)
7. 2" T Pipe Cap Kit
8. Vertical Post
9. 2" Post Base Kit
10. Grounding Lug
Module Area (sq.ft.)880
Crow Wing Power
POINT LOAD CALCULATION PER ARRAY 2
Module Weight (lbs)
# Of Modules
48.5
Total Module Weight (lbs)
Rack Weight (lbs)
Total System Weight (lbs)
# Of Standoffs
Max Span Between Standoffs (in)
Loading Per Standoff (lbs)
Loading (PSF)
1455
291
1746
18
96
97
2.64
30
Module Area (sq.ft.)660
8'8'8'8'8'8'8'8'
8'8'8'8'8'8'8'8'
6'-6"
3'-5"
3'-5"
6'-6"
1'-9"
1'-9"
65'
65'
ARRAY 1
ARRAY 2
PV 6.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
MONITORING
DATA SHEET
INVERTER
DATA SHEET
D 7.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
RSD
DATA SHEET
D 8.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
MODULE
DATA SHEET
D 9.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE:
REVISION DATE:
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE: 09/15/2023
RACKING
DATA SHEET
D 10.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
ATTACHMENT
DATA SHEET
D 11.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
D 12.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
SURGE
PROTECTION
D 13.0
PV SYSTEM AS INDICATED
Scale:Project:
INVERTER
CERTIFICATION
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
D 14.0
PV SYSTEM AS INDICATED
Scale:Project:
PV INSPECTION
CHECKLIST
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
Wolf RIver Electric
Marine on St Croix, MN 5504714025 185th St N
D 15.0
PV SYSTEM AS INDICATED
Scale:Project:
Drawn by: New@engineerinc.io
Project Name:
Property Address:
DATE CREATED:
CONTRACTOR
Wolf RIver Electric
Address:101 Isanti Parkway
NE, Isanti, MN 55040
Phone number: (763) 229-6662
E-mail: contact@wolfriverelectric.com
REVISION DATE: 08/14/2023
14025 185th St N,
Marine on St Croix, MN 55047
REVISION DATE:
REVISION DATE :
REVISION DATE :
Brian Rigwald
08/11/2023
REVISION DATE:
REVISION DATE : 09/15/2023
CONNECTOR
DATA SHEET