3.d.1 Bliss Collector - WW Inspection ReportCMas Minnesota Pollution Control Agency
520 Lafayette Road North I St. Paul, Minnesota 55155-4194 1 651-296-6300
800-657-3864 1 Use your preferred relay service I info.pca@state.mn.us I Equal Opportunity Employer
June 9, 2016
Hon. Randall Simonson, Mayor
City of Scandia
14727 209th Street North
Scandia, MN 55073
RE: Bliss Collector WWTP
State Disposal System Permit No. MN0054119
Compliance Evaluation Inspection
Dear Mayor Simonson:
Enclosed is the Compliance Evaluation Inspection (CEI) Report that resulted from an inspection of the Bliss
Collector Wastewater Treatment Facility (Facility) on May 24, 2016, by Kaitlin Jamieson of the Minnesota
Pollution Control Agency (MPCA).
The CEI consisted of a visual inspection of the Facility and a discussion with Jeff Anderson -Maintenance
Worker and Dave Williams -Public Works Director. In addition, there was a review of the monthly Discharge
Monitoring Reports (DMRs) for the time period from September 1, 2012 to May 24, 2016. Based on the
results of the CEI, violations of the terms and conditions set forth in the State Disposal System (SDS) permit
were noted. Please see the attached CEI Report for further detail.
To address the violations, the MPCA requests a written response within 30 days of receipt of this report.
If you have any questions, please contact me at 651-757-2306 or kaitlin.jamieson@state.mn.us.
Sincerely,
<av-r" Ye1r"e4v*v
This document has been electronically signed.
Kaitlin Jamieson
Environmental Specialist 2
Municipal and Industrial Wastewater Section
Municipal Division
KJ:wgp
Enclosure
cc: Jeff Anderson, City of Scandia
Neil Soltis, City of Scandia
t-wq-wwprm2-33 • 4118116
Minnesota Pollution Control Agency
Water Quality Point Source Program
Compliance Evaluation Inspection Report
Facility information:
Facility name: Bliss Collector WWTP
Permit number: MN0054119
Address: 18925 Manning Trail, Scandia, Minnesota 55073
SIC code: 4952 - Sewerage Systems
Permit expiration date: February 29, 2020
Facility design flow: 0.02 mgd (AWW)
EPA Facility Type classification: EPA Minor
Type of flow: Domestic
Plant class: Class D
Land application type: Septage
24-hour contact: Public Works Office
Phone: 651433-5223
Geographic information:
MPCA region: MPCA Metro Region
County: Washington
Basin: St. Croix River
Major watershed: Lower St. Croix River
Receiving water: Not applicable
Those present during the inspection:
Jeff Anderson, Maintenance Worker
Dave Williams, Public Works Director
MPCA representatives:
Kaitlin Jamieson, Compliance Inspector
Inspection information:
Inspection date: May 24, 2016
Inspection category: Routine Inspection
Inspection type: WW Compliance Evaluation Inspection
Facility components:
• Collection system (gravity and/or pressure)
• Collection system (gravity septic tank effluent)
• Collection system (pumped septic tank effluent)
• Effluent Disposal - Subsurface Trench/Bed
• Effluent filtration (sand without backwash)
• Individual or Community SSTS
• Primary treatment - septic tank
• Single Pass Media Filter
t-wq-wwprm2-33 • 4118116
Minnesota Pollution Control Agency
Significant industrial users:
4952 - Sewerage Systems
Treatment plant operators:
Jeff Anderson, Class D certification, expires June 1, 2016 (renewal requested)
Service Provider certification, expires February 13, 2019
t-wq-wwprm2-33 • 4118116
Inspection Summary
A Compliance Evaluation Inspection was conducted on May 24, 2016, by Kaitlin Jamieson of the Minnesota
Pollution Control Agency (MPCA) to determine the Facility's compliance with the terms and conditions of its
State Disposal System (SDS) Permit. The following is a summary of the findings and comments resulting
from that inspection.
Areas of Concern or General Comments:
1. Overall Physical Condition of the Facility
a. The Facility appeared well maintained and appeared to be in good operating condition.
b. The Facility grounds were fenced, gated, posted and locked.
2. Sampling Methods/Lab Certification
a. All samples are taken at the appropriate locations as identified in the permit, and are
representative of flow through the Facility and treatment system.
b. Sampling is performed by Facility staff.
c. Samples are delivered to a contract lab for analysis, Pace Analytical Services Inc. — Virginia,
Minnesota, Minnesota Department of Health State lab ID #027-137-445, EPA Lab Code
MN01084. The lab results records are adequate and maintained for a minimum of three years.
d. pH testing is performed on site by the Facility operator. Original pH meter readings and pH
meter calibration logs were not adequately kept. See the Alleged Violations section for further
description.
3. Discharge Monitoring Reports (DMRs)/Sample Values/Annual Reports
a. Several DMRs due over the review period were submitted late.
b. The DATES DMRs and related records were reviewed for reporting accuracy. The monitoring
data was accurately reflected on the DMRs.
c. Daily/Sample values have been submitted with all DMRs.
4. Inflow & Infiltration (1&1)/ Collection System issues
a. The collection system consists of 70 individual septic tanks and 46 shared septic tank effluent
pumping (STEP) systems which pump to one of two lift stations.
b. Lift station pumps are pulled annually for maintenance and cleaning.
c. The main lift station is set to be replaced in the near future.
d. The city of Scandia (City) coordinates pumping the individual septic tanks. Tank levels are
measured annually, and pumped as needed.
e. The Facility experience some I&I issues.
5. Flow data
a. The Facility's design flow is 0.0198 million gallons per day (MGD).
b. The Facility's reported average influent flows over the past several years were:
i. 2013 — 0.007 MGD
ii. 2014-0.010 MGD
iii. 2015-0.007 MGD
iv. 2016-0.008 MGD (to date)
c. The reported three-year average influent flow at the Facility is about 0.008 MGD. The Facility
appears to be operating at approximately 40 percent of the permitted design capacity.
d. WS001 pumps are used to monitor flow for permit reporting. Pump run times are recorded
daily. The operators can remotely access pump run time information.
e. Pumps are pulled annually for cleaning, maintenance and calibration. Pump calibration records
are stored electronically and have been maintained for three years.
t-wq-wwprm2-33 • 4118116
6. Enforcement Actions over the review period
a. None.
7. Compliance Schedule progress
a. A Compliance Schedule was included in the current permit due to concerns with the Facility's
ability to consistently meet the state drinking water standard for nitrate at monitoring well
GW -004.
b. The Compliance Schedule required a Nitrogen Mitigation Plan (Plan) be submitted by March 18,
2016. A Plan was submitted to the MPCA on March 14, 2016, but it did not include all the
required information. The City has hired the firm Bolton & Menk to assess the treatment
system and prepare a detailed Plan. The Plan should be completed and submitted to the MPCA
promptly.
c. A final report is required September 2, 2019 (180 days prior to permit expiration).
i. Permit Chapter 1, section 1.2. The report shall serve as a performance report and
summarize the treatment system's ability to consistently achieve compliance with the
Minnesota Department of Health (MDH) drinking water standard of 10 milligrams per
liter (mg/L) for Nitrate Nitrogen at either the end of discharge of the treatment facility
or within the downstream monitoring wells. The performance report shall include, if
necessary, what is needed to maintain compliance with the MDH standard of 10 mg/L,
including recommendations concerning modifications to the facility design, operation,
and/or maintenance.
8. Biosolids/Land Application Sites
a. The 2013 and 2015 Biosolids Annual Reports due over the review period were submitted late.
See the Alleged Violations section for further description.
9. Pretreatment
a. Not applicable. Only residential homes are connected to the Facility.
10. General Maintenance Schedule
a. Operation and Maintenance manuals for Facility components were maintained on site.
b. The general maintenance schedule was appropriate and followed.
c. Facility grounds and drainfields are mowed a couple times each year, as needed.
d. There were some signs of gopher mounds on site. The operators control gophers as needed.
e. Facility tanks are pumped approximately each year.
f. Two of the three drainfields were being operated. Drainfield number two has been rested for a
couple years to try and minimize impacts to monitoring well GW -004.
g. There are three sand filters, and each year the operator rotates which filters are in use.
11. Record Keeping
a. Most required records were neatly kept and available upon request.
12. Other
a. There were no unauthorized releases or overflows reported over the review period.
t-wq-wwprm2-33 • 4118116
Alleged violations/description of non-compliance table:
#
Citation
Requirement
Results or Comments
1
SDS Permit Number
The Permittee shall comply with the limits and monitoring
The Permittee exceeded the limit for
MN0054119; Limits and
requirements as specified.
Flow, Daily Maximum. See Table 1
Monitoring Requirements
below for specific exceedances.
2
SDS Permit Number
1.1. The Permittee shall submit a Nitrogen Mitigation Plan for
The Permittee submitted an
MN0054119; Chapter 1
MPCA approval within one year of permit issuance. This plan shall
incomplete Nitrogen Mitigation Plan.
Compliance Schedule; Section
serve as a monitoring and evaluation plan for documenting the
1. Compliance Schedule
treatment effectiveness of the treatment system components.
Nitrogen Mitigation Plan;
The Plan shall include an overall assessment of the entire
subpart 1.1.
treatment system at the facility, along with recommendations
and any potential changes to the engineering design for lowering
the Total Nitrogen entering the soil dispersal system. By lowering
the Total Nitrogen prior to disposal, it may be possible to lower
the elevated Nitrates detected in the on-site monitoring well
G W004.
3
SDS Permit Number
7.1. By December 31 following the end of each cropping year, the
The Permittee submitted the 2013
MN0054119; Chapter 5.
Permittee shall submit a Biosolids Annual Report for the land
and 2015 Biosolids Annual Reports
Domestic Wastewater —
application of biosolids on a form provided by or approved by the
late. The 2013 report was due by
Biosolids Domestic Septage (No
MPCA. The report shall include the requirements in Minnesota
December 31, 2013, but was
Analysis Required); Section 7.
Rules, part 7041.1700.
submitted late on January 29, 2014.
Reporting Requirements;
The 2015 report was due by
subparts 7.1. and 7.2.
7.2. The permittee shall submit a Biosolids Annual Report by
December 31, 2015, but was
December 31 of each year for biosolids storage and/or transfer
submitted late on March 15, 2016.
and
activities occurring during the cropping year previous to
December 31. The report must indicate whether or not biosolids
The Permittee submitted several
Chapter 7. Total Facility
were transferred and/or stored. If biosolids were transferred, the
DM Rs late. See Table 2 below for
Requirements; Section 1.
report must describe how much was transferred, where it was
specific late or non -submitted
General Requirements, subpart
transferred to, the name of the facility that accepted the transfer
reports.
1.23.
and the contact person at that facility. "Cropping year" means a
year beginning on September 1 of the year prior to the growing
season and ending August 31 the year the crop is harvested. For
example, the 2012 cropping year began September 1, 2011, and
ended August 31, 2012.
t-wq-wwprm2-33 • 4118116
t-wq-wwprm2-33 • 4118116
1.23. Submitting Reports. Electronic Discharge Monitoring
Reports (eDMRs), DMR Sample Values and/or Operational
Spreadsheets or DMR Supplemental Forms, and related
attachments shall be submitted electronically via the MPCA
Online Services Portal after authorization is approved.
Authorization must be applied for and approved prior to
submittal via the Online Services Portal.
eDMRs and DMR Sample Values and/or Operational Spreadsheets
or DMR Supplemental Forms shall be electronically submitted by
the 21st day of the month following the monitoring period end or
as otherwise specified in this permit. Electronic DMR submittal
must be complete on or before 11:59 PM of the 21st day of the
month following the end of the monitoring period or as otherwise
specified in this permit. A DMR shall be submitted for each
required station even if no discharge occurred during the
monitoring period. (Minn. R. 7001.0150, subps. 2.13 and 3.H)
4
SDS Permit Number
1.18. Certified Laboratory. A laboratory certified by the
The Permittee did not properly verify
MN0054119; Chapter 7. Total
Minnesota Department of Health and/or registered by the MPCA
or calibrate meters used for on-site
Facility Requirements; Section
shall conduct analyses required by this permit. Analyses of
analysis including pH, specific
1. General Requirements;
dissolved oxygen, pH, temperature, specific conductance, and
conductance, and temperature.
subparts 1.18, 1.20, and 1.21.
total residual oxidants (chlorine, bromine) do not need to be
completed by a certified laboratory but shall be completed by
The Permittee did not verify or
equipment that is verified for accuracy before use. (Minn. Stat.
calibrate the pumps used for flow
Sec. 144.97 through 144.98 and Minn. R. 4740.2010 and
monitoring at least twice annually.
4740.2050 through 4740.2120) [Minn. R. 4740.2010]
Pump calibrations are performed
once per year.
1.20. Equipment Calibration: Flow meters, pumps, flumes, lift
stations or other flow monitoring equipment used for purposes of
The Permittee did not maintain
determining compliance with the permit shall be verified and/or
original records of sample time and
calibrated for accuracy at least twice annually. [Minn. R.
analysis time for sampling and
7001.0150, subp. 2]
monitoring that is performed on site.
1.21. Maintain Records. The Permittee shall keep the records
required by this permit for at least three years, including DMRs,
inspections, calibration and accuracy verifications, maintenance
records, any calculations, original recordings from field or
t-wq-wwprm2-33 • 4118116
Table 1. Limits and Monitoring Requirements Exceedances
Station
Parameter Limit
automatic monitoring instruments, laboratory sheets, chain of
Reported Value
Limit Type
Reporting Period
custody forms, copies of all reports required by the permit, and all
Flow 0.0297
mgd
0.032
data used to complete the permit application. The Permittee shall
5/1/2013 — 5/31/2013
WS001
Flow 0.0297
extend these record retention periods upon request of the MPCA.
0.035
Daily Maximum
6/1/2013 — 6/30/2013
a. The exact place, date, and time of the sample or measurement;
Flow 0.0297
mgd
0.0571
b. The date of analysis;
4/1/2014-4/30/2014
WS001
Flow 0.0297
c. The name of the person(s) who performed the sample
0.0397
Daily Maximum
6/1/2014-6/30/2014
collection and/or measurement;
8/25/2015
GWO11
7/1/2015 — 7/31/2015
d. The name of the person(s) who performed the analysis and/or
8/25/2015
GWO12
7/1/2015 — 7/31/2015
calculation;
8/25/2015
e. The analytical techniques, procedures and methods used; and
f. The results of the analysis.
Table 1. Limits and Monitoring Requirements Exceedances
Station
Parameter Limit
Units
Reported Value
Limit Type
Reporting Period
WS001
Flow 0.0297
mgd
0.032
Daily Maximum
5/1/2013 — 5/31/2013
WS001
Flow 0.0297
mgd
0.035
Daily Maximum
6/1/2013 — 6/30/2013
WS001
Flow 0.0297
mgd
0.0571
Daily Maximum
4/1/2014-4/30/2014
WS001
Flow 0.0297
mgd
0.0397
Daily Maximum
6/1/2014-6/30/2014
Permitted flow limits were exceeded as shown in the table.
Table 2. Discharge Monitoring Reports Submitted Late
Station
Reporting Period
DMR Due Date
DMR Submittal Date
WS001
5/1/2015 — 5/31/2015
6/21/2015
6/25/2015
GWO01
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO04
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO06
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO08
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO09
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO10
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO11
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO12
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
t-wq-wwprm2-33 • 4118116
GWO13
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO14
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO15
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO16
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
GWO17
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
WS001
7/1/2015 — 7/31/2015
8/21/2015
8/25/2015
WS001
8/1/2015 — 8/31/2015
9/21/2015
Not submitted
WS002
6/1/2015 — 9/30/2015
10/21/2015
5/24/2016
WS001
12/1/2015 — 12/31/2015
1/21/2016
4/21/2016
WS001
2/1/2016 — 2/29/2016
3/21/2016
4/12/2016
WS001
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO01
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO04
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO06
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO08
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO09
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO10
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO11
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO12
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO13
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO14
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO15
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO16
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
GWO17
4/1/2016 — 4/30/2016
5/21/2016
Not submitted
Required DMRs were submitted late or not submitted as shown in the table.
t-wq-wwprm2-33 • 4118116
Corrective Action Section:
1. Within 30 days of receipt of this CEI, the Permittee shall summarize the cause of the permit limit
exceedances and describe any actions taken to ensure these do not occur in the future.
2. Within 30 days of receipt of this CEI, the Permittee shall submit a complete Nitrogen Mitigation
Plan.
3. Within 30 days of receipt of this CEI, the Permittee shall summarize the cause of the late reports
and describe what actions have been or will be taken to ensure all reports are submitted on
time in the future.
4. Within 30 days of receipt of this CEI, the Permittee shall submit a summary to the MPCA
demonstrating how adequate records will be maintained for at least three years including
records of equipment calibrations on meters used for on-site analysis, flow meter verification or
calibrations performed twice annually, and original sampling records that include sample time
and analysis time.
STATE OF MINNESOTA
POLLUTION CONTROL AGENCY
June 9, 2016 <�" �G�rwtel-On.
Date signed This document has been electronically signed.
Kaitlin Jamieson
Environmental Specialist 2
Municipal and Industrial Wastewater Section
Municipal Division
Address questions and submittals requested above to:
Kaitlin Jamieson
Minnesota Pollution Control Agency
520 Lafayette Road North
St. Paul, Minnesota 55112
651-757-2306
kaitlin.jamieson@state.mn.us