5. Anderson Erickson lift station and drainfieldBO L—rC:>" 8L. M F== N IAC ,
f Consulting Engineers & Surveyors
" 12224 Nicollet Avenue • Burnsville, MN 55337
Phone (952) 890-0509 • Fax (952) 890-8065
www.bolton-menk.com
MEMORANDUM
Date: 3/21/16
To: Seth Peterson, P.E.
Ryan Goodman, P.E.
From: Morgan Salo, E.I.T.
Subject: A/E Lift Station and Drain field
Scandia, MN
r ---j Ce
The Anderson/Erickson drain field was designed to treat up to 6,700 gallons per day. The report
that analyzed the existing system states that the drain field is only being operated with half of the
designed infiltration area with flows exceeding 7,500 gallons per day during the peak summer
months, starting in 2006. The report indicates that it is likely that flows are exceeding 10,000
gallons per day.
The lift station contains two — 5 HP grinder pumps designed to deliver 50 gallons per minute.
Based on drawdown testing, pump no. 1 can produce 60 gpm and pump no. 2 can produce 59
gpm. Analysis of historic pump run data show is shown in Table 1 below.
Table 1: Historic Pump Run Times
Year
Peak Day Flow
(gal/day)
2013
9,867
2014
11,588
2015
5,134
Typically, the highest flows occurred between April and July for each year, with peak flows
exceeding the design capacity of 6,700 gallons per day of the system. Peak flows for each year
were determined by first finding the peak day flow for the entire year. The peak flow was then
determined by taking the seven day average of the previous three days, the peak day, and the
three days after the peak. 2013 and 2014 have peak flows that exceed the design capacity of the
system. Generally, the flows in 2014 were higher than any other year. Flows commonly
Anderson Erickson Drain field Evaluation
DESIGNING FOR A BETTER TOMORROW
Bolton & Menk is an equal opportunity employer.
0
Page 2
exceeded 10,000 gpd from January through May. The rest of the year saw flows ranging from
5,500 gpd to 9,894 gpd. The flows in 2015 were typically low. The peak flow occurred on July 7
with a total flow of 9,870 gpd. The 7 day average was calculated to be 5,134 gpd. For a majority
of the year, the flows were approximately 50% of the design capacity of the system.
Using the historic flows, an estimate of how many houses can be connected to the system can be
determined. Septic systems are designed based on volume of water per person per bedroom in a
house. The design standard for Minnesota is 150 gpd/bedroom. This assumes that there are two
people per bedroom. Using this criteria, and assuming each house has four bedrooms, the total
flow from each house would be 600 gpd into the system.
Using the 2013 and 2014 flows, the peak flows exceed the design capacity by 32% and 42%,
respectively, allowing no more houses to be added onto the system. However, using 2015 peak
flows, another three, four bedroom, houses can be added onto the system before the system
exceeds the design capacity of 6,700 gallons per day.
Anderson Erickson Drain field Evaluation
DESIGNING FOR A BETTER TOMORROW
Bolton & Menk is an equal opportunity employer.
Consulting Engineers & Surveyors
" 12224 Nicollet Avenue • Burnsville, MN 55337
Phone (952) 890-0509 • Fax (952) 890-8065
www.bolton-menk.com
Table 3: 2013 A/E Flow
Month
Avg.
(gal/day)
Peak
(gal/day)
January
3260
5300
February
3913
5300
March
3723
5300
April
7611
12066
May
4651
8784
June
4636
6116
July
5004
8985
August
4134
5591
September
3763
5591
October
3267
4416
November
6866
7944
December
7072
9564
Average/Max
4825
12066
Table 4: 2014 A/E Flow
Month
Avg.
(gal/day)
Peak
(gal/day)
January
7643
18762
February
7605
10320
March
8270
15042
April
9180
19128
May
5565
11784
June
5276
9894
July
5457
8619
August
3518
5502
September
2488
4956
October
2284
4248
November
2507
5502
December
3431
9540
Average/Max
5269
19128
Anderson Erickson Drain field Evaluation
DESIGNING FOR A BETTER TOMORROW
Bolton & Menk is an equal opportunity employer.
Table 5: 2015 A/E Flow
Month
Avg. Peak
(gal/day) (gal/day)
January
2097
3330
February
2633
3660
March
2478
3282
April
2549
3660
May
2377
3306
June
2523
3306
July
3643
9870
August
2502
3660
September
2610
3755
October
2227
2928
November
2568
5856
December
2662
3536
Average/Max
2572
9870
Anderson Erickson Drain field Evaluation